Operational Tests
Important: Review the warranty policy before performing any intrusive maintenance procedures. An extended warranty may be voided if intrusive maintenance is performed during this period.
Every 12 months perform the operational tests as listed below.
- Start the engine, build air pressure in the air brake system,
and check the pressure registered by a dash or test gauge at the time
the governor cuts out, stopping the compression of air by the compressor.
The cutout pressure should be in accordance with the pressure setting
of the piece number being used. Common cutout pressures are between
125 to 135 psi (862 to 931 kPa).With the engine still running, make a series of brake applications to reduce the air pressure and observe at what pressure the governor cuts in the compressor. As in the case of the cutout pressure, the cut-in pressure should be in accordance with the pressure setting of the piece number being used. Cut-in pressure is 105 psi (724 kPa).As in the case of the cutout pressure, the cut-in pressure should be in accordance with the pressure setting of the piece number being used. Cut-in pressure is 105 psi (724 kPa).
- Never condemn or adjust the governor pressure settings
unless they're checked with an accurate test gauge or a dash gauge
that's registering accurately. If the pressure settings of the D-2
governor are inaccurate or it's necessary that they be changed, the
adjustment procedure follows.
- Remove the top cover from the governor.
- Loosen the adjusting screw locknut.
- To raise the pressure settings, turn the adjusting screw counterclockwise. To lower the pressure settings, turn the adjusting screw clockwise. Be careful not to overadjust. Each 1/4 turn of the adjusting screw raises or lowers the pressure setting approximately 4 psi (28 kPa).
- When proper adjustment is obtained, tighten the adjusting screw locknut and replace the cover. The pressure range between cut-in and cut-out is not adjustable.
Cut-In Position
Apply soap solution around the cover and to the exhaust port. Slight bubble leakage is permitted. Excessive leakage indicates a faulty inlet valve or faulty lower piston O-ring.
Cut-Out Position
Apply soap solution around the cover and to the exhaust port. Slight bubble leakage is permitted. Excessive leakage indicates a faulty exhaust valve seat, exhaust stem O-ring, or O-ring at the top of the piston.
If the governor does not function as described, or if leakage is excessive, it is recommended that it be replaced with a new or remanufactured unit, or repaired with genuine Bendix parts.
Note: If the governor cover is marked nonadjustable, and the adjusting stem has been sheared off, this is a non-serviceable governor and it must be replaced with a new or remanufactured unit.